NUT on my Pi, so my servers don't die

A few weeks ago, power went out for the first time in my studio space, and that meant all my servers just had power cut with no safe shutdown.
Handling power outages is never a top priority... until it's the only priority! And by then it's usually too late! Luckily for me, no data was lost, and my servers all came back up safely.
This week the power company emailed and said they'd be cutting power for maintenance next week, but they don't have an exact time. So it's even more excuse to finally set up NUT on a Pi!
NUT, short for Network UPS Tools, is an open source tool you run on an old Pi or whatever old computer, and it monitors UPSes like the Lowell Power UPS in my main rack. NUT clients, then, can monitor the UPS through the Pi, and safely shut down before the battery is depleted.
Video
I have a full video going over my setup, along with a walkthrough of my end-to-end UPS power fail test, over on my YouTube channel. You can also watch it below (or scroll past and read through the instructions on the blog!):
Setting up a Pi as a NUT server
First, flash Pi OS (I used Pi OS Bookworm 'Lite') to a microSD card and plug that into your Pi. Boot up the Pi, make sure you can log into it over SSH, and then begin the process of setting up NUT.
For my Pi, I mounted it in the back of my rack with this Raspberry Pi Rack Mount on Printables (printed in ASA), and I just powered it off a USB-C power adapter, which is plugged into the PDU behind my rack UPS.
Since NUT doesn't require much in the way of resources, you can run it on most any Pi model—the Pi I used was an old Compute Module 4 with 1 GB of RAM I had laying around, mounted in a BigTreeTech Pi4B CM to Pi 4 adapter board.
Configuring a UPS for NUT
Before doing anything else, install NUT with sudo apt install -y nut. This will install nut-client, nut-server, and other UPS tools you will use later
Then, assuming you have your UPS plugged into a USB port on your Raspberry Pi, run nut-scanner, and see what it finds:
$ sudo nut-scanner -U
Scanning USB bus.
[nutdev1]
driver = "nutdrv_qx"
port = "auto"
vendorid = "0665"
productid = "5161"
product = "UPS"
bus = "001"
You can take those values, and use them in your UPS configuration (assuming you just have one UPS connected). Edit NUT's ups.conf file with sudo nano /etc/nut/ups.conf and add your UPS configuration. For example:
[server-room-rack]
driver = nutdrv_qx
product = UPS
desc = "Server Room Lowell Power Rack UPS"
port = auto
vendorid = 0665
productid = 5161
bus = 001
The name of the UPS (in my case, server-room-rack) should be ASCII characters with no spaces or special characters besides -.
Save that file and close it.
Note: If you can't connect to your UPS, or the scanner doesn't find it, read through the NUT documentation on UPS drivers to see if you might be missing something. You don't have to use a USB connection, though it's the most common across all the modern UPSes I've used.
Setting up NUT server
To make the Pi run as a NUT Server, and not just for local monitoring, edit the upsd.conf file with sudo nano /etc/nut/upsd.conf and add a LISTEN directive:
LISTEN 0.0.0.0 3493
Save that file and close it.
You'll also need to define a list of NUT users who will be able to manage the UPS either locally or over the network. Edit upsd.users with sudo nano /etc/nut/upsd.users and add something like the following:
[admin]
password = ADMIN_PASSWORD_HERE
actions = set
actions = fsd
instcmds = all
upsmon primary
[observer]
password = OBSERVER_PASSWORD_HERE
upsmon secondary
The admin user will have full access to do anything, including immediately send out a shutdown command (fsd) to all connected systems. So... don't use that account for all the clients, it's just for admin tasks!
The observer account is what I use on all my NUT clients to connect back and monitor the main UPS.
Configure the UPS monitor on the NUT Pi by editing upsmon.conf, using sudo nano /etc/nut/upsmon.conf:
# Make sure you use your actual admin password...
MONITOR server-room-rack@localhost 1 admin ADMIN_PASSWORD_HERE primary
# You might also want to configure FINALDELAY and set it to a period long enough
# for your servers to all shut down, prior to the primary node shutting down and
# triggering the UPS to switch off its load, e.g. for 3 minutes:
FINALDELAY 180
Save and close the file, then edit nut.conf (with sudo nano /etc/nut/nut.conf) and change the MODE from none (default) to netserver:
MODE=netserver
Restart the NUT server and make sure it is enabled at system boot:
sudo systemctl restart nut-server
sudo systemctl enable nut-server
sudo systemctl restart nut-monitor
sudo systemctl enable nut-monitor
Confirm NUT works
Check if you can see all your UPS details with upsc [ups-name-here]:
$ upsc server-room-rack
Init SSL without certificate database
battery.charge: 24
battery.energysave: no
battery.packs: 1
battery.protection: yes
battery.runtime: 0
battery.voltage: 50.60
battery.voltage.nominal: 48.0
device.model: LILVX2K0
device.type: ups
driver.name: nutdrv_qx
...
If you want to see a fancy web UI, a few of those exist (like nut_webgui), but in my case, I have Home Assistant, and monitor all the vitals in there. Home Assistant has an official NUT integration that automatically identified the NUT Pi over the network after I added the Integration to my HA install. All I had to do was add the observer username and password.
Then I created a simple card with the most important UPS statistics in one of my HA dashboards:

The YAML for that card, in case you want to replicate it, is:
type: vertical-stack
title: Server Room Rack UPS
cards:
- type: history-graph
entities:
- name: Status
entity: sensor.server_room_rack_status
hours_to_show: 4
- type: gauge
entity: sensor.server_room_rack_battery_charge
name: Battery Charge
severity:
green: 50
yellow: 20
red: 0
Just to show what the Docker-base nut_webgui looks like, though, I launched an instance on my Mac (localhost) using the command:
docker run \
-e UPSD_ADDR=10.0.2.10 \
-e UPSD_USER=observer \
-e UPSD_PASS=PASSWORD_HERE \
-p 9000:9000 \
ghcr.io/superioone/nut_webgui:latest
And it has a pretty complete dashboard with stats for all connected UPSes. Clicking on one brings up a fancy details page with every metric and configurable option available:

Setting up a NUT Client on other nodes
The NUT Server will shut down last, after sending an fsd notice out to all connected clients. But your other servers need to be configured with nut-client before they will connect!
On each of your servers you want to have shut down cleanly with your primary UPS, set up the client and configure it to connect back:
- Install
nut-client:sudo apt install nut-client - Verify connection to server:
upsc server-room-rack@IP_ADDRESS(whereIP_ADDRESSis the IP of the NUT Pi server) - Configure NUT's UPS monitor for client:
sudo nano /etc/nut/upsmon.confand add aMONITORline: -MONITOR server-room-rack@IP_ADDRESS 1 observer PASSWORD secondary(whereIP_ADDRESSis the IP of the NUT Pi server, andPASSWORDis the observer password) - Edit
/etc/nut/nut.confand setMODE=netclient(change from defaultnone) - Restart and enable
nut-client: -sudo systemctl restart nut-client-sudo systemctl enable nut-client
Each server where you have nut-client running should be tracking the primary NUT server, and should shut down if it sends out an fsd notice.
Monitoring NUT server and clients
If you want more verbose logs, you can set the NUT_DEBUG_LEVEL environment variable when restarting the NUT services, but by default, it will log important notifications and things like the UPS going from 'online' to 'battery'.
# On server
journalctl -f -u nut-server
# On client
journalctl -f -u nut-monitor
Managing the connected UPS
On the NUT Pi server, you can use upscmd to manage the connected UPS, using the admin user, for example:
# List commands supported on this UPS
upscmd -l server-room-rack
# Run a quick battery test (requires password)
upscmd -u admin server-room-rack test.battery.start.quick
Debian 12 upsmon bug
When I did this last command, I unintentionally triggered a bug with the current version of nut-client on Debian 12... if a UPS self-test is run, the 'CAL' flag is set (calibration), and while it's set, any critical UPS battery alerts are ignored! (See the original NUT bug report.)
There's a bug report in Debian currently: CAL flag in UPSMON never cleared, shutdown procedure will not be triggered, and one workaround is to restart nut-client (sudo systemctl restart nut-client) on a cron job, maybe every hour, or if you know your UPS self-test schedule, immediately following.
Testing NUT
There are three different layers of testing you can do, to verify NUT is running correctly.
NOTE: These options could result in data loss! Make sure you're not doing any critical activities on the systems while you're testing your power setup...
1 - NUT Debug / test mode
I... never tried this, but apparently you can do a 'soft test' following the instructions in Dan Langille's blog: nut – testing the shutdown mechanism
2 - Live test of NUT without unplugging UPS
You can trigger the fsd event manually on the NUT Pi server with:
upsmon -c fsd
That will immediately emulate the condition of the UPS status OB LB (On Battery / Low Battery), which tells all connected systems to run their shutdown command.
3 - Live end-to-end test with UPS on battery
Unplug your UPS. Monitor the stats with upsc (like upsc server-room-rack, for mine), and validate the various parameters are correct for your UPS.
Wait a while, and keep an eye on metrics like:
$ upsc server-room-rack
battery.charge: 32
...
battery.voltage: 51.30
...
ups.load: 11
...
ups.status: OL
At some point, the UPS will have a status like OL LB or ALARM OB, and NUT should trigger shutdowns on all your connected NUT clients.
Conclusion
There are a number of options you can set on both the NUT server and clients which I've not covered in this post. The documentation is pretty dense, but readable.
The defaults are good for most use cases, but you might want to trigger an FSD earlier, before your UPS goes into 'LB' or Low Battery state. This might be useful if you have a high-power-draw server that takes 5-10 minutes to shut down. You could have it shut down when the battery's at 50% or has X minutes remaining, instead of waiting to the very end.
I'm automating my NUT setup, so it's easier to apply uniformly against all my servers, and here are the Ansible projects I'm using: